The Touch Screen Controller is an advanced central controller, which is available in various different formats. It is available in four formats, to control sixty-four or five hundred and twelve indoor units, each of which are available with or without the billing function. The Touch Screen allows full unit control of all connected indoor units and is capable of giving full fault and operating information. The controller has the ability to schedule on/off times for each individual indoor unit.

The Touch Screen is compatible with all SMMS/SHRM systems DI and SDI systems may also be added, but network adapters are required.
 


Application

The Touch Screen would be used in an application where multiple unit control is required from one location. The Touch Screen can be combined with other components to provide energy monitoring or a common fault input/output signal, which could be used for a fire alarm shutdown or similar facility. If the billing function is used a PC running Excel is required.
 

Connections

The Touch Screen connects to an RS485 Network, which links the screen to the Relay Interfaces. The Relay Interfaces are then connected to the Air Conditioning Network via the U3 & U4 connection. The RS485 Network also connects to the power meter and digital input/out interfaces. If the energy monitoring facility is being used a separate PC will be required to run the energy monitoring software.

This PC will require Microsoft Excel and will need to be connected to the Touch Screen via a network connection. The Touch Screen requires a 240V 3A mains power supply
 

Additional Components

TCS Net Relay Interface BMS-IFLSV2E2

The Relay Interface connects to the Touch Screen Controller via the RS485 Network using connections A & B. The air conditioning network connects to terminals U1 & U2 (U3 & U4 at the outdoor unit) and a maximum of 64 Indoor units may be served. The relay interface requires a 240V 3 A mains power supply.

Energy Monitoring Relay Interface BMS-IFWH4E2

The energy monitoring Relay Interface connects to the RS485 Network and provides a means of interface to the pulse power meters. Up to eight power meters can be connected to each Relay Interface.

Digital Input Output Relay Interface BMS-IFDD02E2

The D/I module connects to the RS485 network and provides 8 inputs and 4 outputs, which could be used to interface a fire alarm system or a room occupancy sensor. The D/I module output could be used as a means of remote fault indication to another system.
 

Software

Site-specific software is written for the Touch Screen, which gives specific names and locations for easy end-user operation. The software also configures the D/I module and the Energy Monitoring Interfaces.

Energy monitoring software is installed on a separate PC. The software being Excel based and using Macros to produce the reports for each Tenant.
 

Limitations

The total length of the U1/U2 network for each relay interface is as follows

1.5mm2 Screened up to 1000m
2.5mm2 Screened up to 2000m
The total length of the RS485 Network A/B
1.5mm2 Screened up to 500m
 

Components

Touch Screens

BMS-TP0641ACE Touch screen for 64 indoor units
BMS-TP0641PWE Touch screen for 64 indoor units with energy billing
BMS-TP5121ACE Touch screen for 512 indoor units
BMS-TP5121PWE Touch screen for 512 indoor units with energy billing

Interface Components

BMS-IFLSV2E2 TCS Net Relay Interface
BMS-IFWH4E2 Energy Monitoring Relay Interface
BMS-IFDD02E2 Digital Input Output Relay Interface
 