TOSHIBA > TCC LINK CONTROLS > TCB-SC642TLE

 

 

 

-  Control up to 64 indoor units individually
-  Volt free inputs
- Up to four controllers per network
- Fault coding
- Connect to DI/SDI via PCNT30TLE

TCB-SC642TLE
TCC CENTRAL CONTROLLER
DI / SDI & VRF

TCB-SC642TLE

The central controller is a product that is capable of controlling 64 indoor units from a single location. The device has the facility to set all of the operating parameters for individual or zoned indoor units, whether they are VRF or individual split systems. It is also capable of displaying individual fault codes for any units on the network.

 

Application

The controller is normally used on an installation where there are multiple indoor units in one location. It gives the ability to link multiple refrigerant systems together for time clock control and to give an indication of any faults within the systems. There are auxiliary inputs for on/off control and relay outputs for remote run and fault indication. It is possible to connect up to ten central controllers on one network, which controls up to 64 master indoor units from multiple locations.
 

Connections

The controller requires a 240 Volt single phase 3 Amp power supply, which connects directly to the mains input terminals on the rear of the device.

The two-core network cable should be screened and have a minimum cross-sectional area of 1.5mm for networks of up to 1000 meters. This should be increased to 2.5mm for networks of 1000 to 2000 meters total length. The network cable terminates at the U1/U3 and U2/U4 connections on the rear of the device.

Terminals A1, A2 and A3 are used to remotely operate all of the connected indoor units.

The indoor units can be enabled with a pulse voltage of 24 Volts applied for 0.5 seconds between terminals A1-A3 and disabled by applying the same voltage between terminals A2-A3.

Terminals B1, B2 and B3 provide dry contact outputs for connection to other systems. A relay contact will close between B3 and B1 indicating system operation and B3 and B2 indicating a fault on any connected units.

Terminal CN02 can be used to connect a 7day timer (RBC-EXW21E) or alternatively the RBC-SMTI interface lead can be connected and used as a means of remote switching.
 

Limitations

Individual control of 64 master indoor units, (7 slave units per master possible) All indoor units will be affected by any timer functions or remote operation signals.

 


Downloads


TCB-SC642TLE - Operating Manual
TCB-SC642TLE - Installation Manual

 