TOSHIBA > TCC LINK CONTROLS > TCB-IFCB-4E

 

 

 

- External on/off
- Monitoring on/off status
- Monitoring Alarm status
 

TCB-IFCB-4E
ON/OFF CONTROL BOX
DI / SDI & VRF

TCB-IFCB-4E

The device is designed to give remote on/off control, operation and remote fault indication for DI/SDI/SMMS/SHRM systems. The device may be connected to single indoor units or one device may be connected to a group of indoor units.

 

Application

The device would typically be used where it was necessary to remotely enable or disable a system and provide a means of operation and fault monitoring. An example of this would be a simple and cost effective means of integration to an existing BMS system.
 

Connections

The device is enclosed in a galvanized steel enclosure, which should be mounted adjacent to the indoor unit and connected to the indoor PCB via the CN61 socket.  The power supply for the device is obtained from the indoor unit supply terminals.
 

Limitations

The output contacts for operation/fault indication are limited to 230 Volts and 0.5 Amps.

ON/OFF control cabling is limited to 500m using 2-core 0.75mm2 cable.

Operation/fault output cabling is limited to 200m when using 3-core 0.75mm2 cable or 400m when using 1.5mm2 cable.

Enclosure Dimensions: 66 x 170 x 200
 