The address setting is carried from a standard
RBC-AMT21/31E remote controller.
Where units do not have standard remote
controllers installed, one should be temporarily attached in
order to carry out the configuration process.
Accessing the Engineers configuration menu
Press Set CL & Check Simultaneously for 4
seconds.
Navigate to menu item 12 (refrigerant line
address) using the Temperature Set Buttons.
Set a unique line address using the Timer Set
Buttons and then press SET.
Navigate to menu item 03 (network address) using
the Temperature Set Buttons.
Set a unique network address using the
Temperature Set Buttons and then press SET
Press the CHECK button to complete the setting
process
Generally speaking the refrigerant line address
would mirror the network address, however this would not be the
case with grouped units, which would have the same network
address but different line addresses.