TOSHIBA > TCC LINK CONTROLS > RBC-PCIN2E

 

 

- VRF Fault Indication
- Outdoor PCB Connection
 

RBC-PCIN2E
OPERATION & FAULT PCB

RBC-PCIN2E

The device is designed for use on the SMMS/SHRM systems and consists of a PCB, which provides a relay contact closure when the system is operating or in the event of a fault.


Application

The device is mounted in the outdoor electrical enclosure and is connected to the interface PCB via terminal CN511 on the header unit. The device would typically be used where a remote operation and fault signal may be required, (critical areas).

Connections

The PCB is connected to the outdoor interface PCB CN511 where indicated. The relay outputs of the PCB are then connected to the required indicators. (see diagram below)
 

Limitations

The maximum distance the contacts can be from the PCB mounted in the outdoor unit is 500M is a 2 or 3 core 0.75mm screened cable is used.


Downloads


Wiring Diagram