TOSHIBA > TCC LINK CONTROLS > RBC-PCOS1E

 

 

- DI Noise Reduction
- DI Power Consumption Limiter
- Outdoor PCB Connection
 

RBC-PCOS1E
DI OUTDOOR LIMITER

RBC-PCOS1E

The device is intended for installation on the DI outdoor unit range and has been designed to limit the outdoor unit noise production in the cooling mode by 5dB, limit the maximum power consumption and give a compressor operation signal. The noise and power functions are individually initiated by a relay contact closure, which may be a time clock, switch or any other suitably rated device. The compressor operation signal is given via a volt free contact closure.

 


Application

The device would be used where it was necessary to limit noise production at certain times of the day, typically at night in residential areas or where it was necessary to limit power consumption at certain times.

Connections

The PCB and power transformer are mounted in the outdoor unit using the installation kit provided. Electrical connections are required to the outdoor unit supply terminals and the inverter assembly using the connectors supplied.
 

Limitations

Compressor operation contacts are rated at 12-250VDC 10mA-1A

Power peak control is in three stages: 0% 50% 75%

Only one power peak option may be selected at any one time.

 


Downloads


Wiring Diagram

 