- For LonWorks BMS
- Up to 64 Indoor Units
- Connects via U1/U2
- Requires 240V 3A Supply
|
 |
TCB-IFLN640TLE
LONWORKS INTERFACE
TCB-IFLN640TLE
|
The LonWorks gateway is a device that allows
the Toshiba indoor units to be connected to a LonWorks based
BMS. The gateway uses all standard network variables
contained in individual function blocks for each indoor
unit. The gateway can communicate with up to 64 indoor units
on a U1/U2 Network.
|
|
|
Application
The device is used to connect to a LonWorks Network, which many
BMS companies are able to communicate with, (open network
protocol). The LonWorks Gateway is used with Interactive
Intelligence Software (RBC-WP1) and also with the Realtime LTX
solutions for connection to other types of BMS.
All of the data for each indoor unit is
available on the LonWorks Network; there are twenty-nine
standard network variables for each indoor unit, all of which
are available on the gateway.
|
|
Connections
The gateway connects to the air conditioner network via U1 & U2
and the LonWorks network connects via the A & B connection. A
240V 3A mains supply is required for the gateway.
|
|
Limitations
The total length of the air conditioner U1/U2
network for each relay interface is as follows.
1.5mm 2
Screened up to 1000m
2.5mm2
Screened up to 2000m
The LonWorks network should be 1.5mm2
Screened up to 500m
|
|
|
Downloads |
 |