TOSHIBA > TCC LINK CONTROLS > RBC-SMTI

 

- Timer interface lead
- 1m Cable
- Connects to controller

RBC-SMTI
TIMER INTERFACE LEAD

RBC-SMTI

The interface lead consists of a 1 meter two core cable and connector, designed for direct connection to the following accessories:

RBC-AMT21E (first generation wired remote controller)

RBC-AMT31E (second generation wired remote controller)

TCB-SC64TLE (central remote controller)

TCB-CC163TLE2 (on/off central controller)

 

Application

The interface lead is used to allow single or groups of units connected to the above devices to be enabled or disabled by means of an external contact.

Connections

The interface lead is connected to the CN02 connection, which is also used for interfacing the Weekly Timer option (RBC-EXW21E).
 

Limitations

It should be noted that when the external contact is operated, all connected systems will be enabled or disabled, depending on whether the contact is opened or closed. Individual units cannot be omitted from the on/off control process.

The interface lead may be extended to a maximum total length of 25 meters when using a screened cable, with a cross sectional area of 0.75mm.
 


Downloads


Wiring Diagram

 