TOSHIBA > TCC LINK CONTROLS > RBC-SMCN61

 

 

- ON/OFF
- REMOTE LOCK
 

RBC-SMCN61
ON/OFF LOCK

RBC-SMCN61

The interface lead consists of a 1 meter three core cable, which can connect to any R410A DI/SDI or SMMS/SHRM indoor unit. The accessory allows the indoor unit to be enabled / disabled by a volt free contact closure. It also allows the remote to be locked to prevent the unit being switched on.
 


Application

The interface lead is used to allow single or groups of units connected to a master unit to be remotely enabled by an external volt free contact. Also the ON/OFF function can be locked by a volt free contact.

Connections

The interface lead is connected to the CN61 connector located on the indoor PCB. If this lead is to be used for the ON/OFF function Jumper J05 is to be removed.
 

Limitations

It should be noted that when the external contact is operated, all connected systems will be enabled or disabled, depending on whether the contact is opened or closed. Individual units cannot be omitted from the on/off control process.

The Locking function only locks the operation function however if the remote is locked OFF it is not possible to adjust any functions of the remote.

The interface lead may be extended to a maximum total length of 25 meters when using a screened cable, with a cross sectional area of 0.75mm.
 