TOSHIBA > TCC LINK CONTROLS > RBC-PCM02E

 

 

- External Master On/Off
- Operation Mode Selection
- Night Set Back
- Snow Fan Control

RBC-PCM02E
ON/OFF MODE SELECT PCB

RBC-PCM02E

The accessory is designed to fit into the SMMS or SHRM outdoor unit; it is a PCB that can be used to perform several different functions. The PCB accepts an input that would be volt free from an external source to enable the required function.


Application

For each of the applications listed below the PCB is mounted in the outdoor electrical box and plugs into different connectors to give the following functions:

External Master On/Off

The PCB plugs into CN512 when a contact is made between common and cool all of the units connected to that system will start in their previous mode of operation.

When the contact is made between common and heat the connected units will stop.

An example time switch would be a Sangamo Suntracker ref 0456 these are available from RS or most Electrical Wholesalers
 

Operation Mode Selection Control

The PCB plugs into CN510 when no inputs are present to the PCB the indoor units can independently control their mode. If a contact is made between common and cool the indoor units will be locked in cooling a mode locked will be displayed on any remote controller. If the contact is made between common and Heat the indoor units are locked in that mode.
 

Night Operation (Sound Reduction) Control

The PCB plugs into CN508 when a contact is made between common and cool the night operation is activated. This limits the compressor and outdoor fan speed. The noise level will be reduced to 50dBA at 1M (free field).
 

Snow Fan Control

The PCB plugs into CN509 when a contact is made between common and cool the out door fan is enabled to remove any snow from the condenser.
 

Connection

The PCB is connected to the outdoor interface PCB where indicated to achieve the required function. The PCB is then connected to a switch or relay contact to activate the PCB as required.
 

Limitations

The maximum distance the contacts can be from the PCB mounted in the outdoor unit is 500M is a 2 or 3 core 0.75mm screened cable is used.
 


Downloads


Wiring Diagram - External Master On/Off
Wiring Diagram - Operation Mode
Wiring Diagram - Night Set Back
Wiring Diagram - Snow Fan Control

 