TOSHIBA > TCC LINK CONTROLS > RBC-IT3

 

 

- REMOTE ON/OFF

 

RBC-IT3
DAISEIKAI CONTROL

RBC-IT3

The RBC-IT3PE time switch interface is intended for use with the TOSHIBA Daiseikai range of indoor units and is designed to allow these systems to be externally switched on and off by means of any volt-free external terminals rated at 230 volts a/c.
 


Application

The RBC-IT3-PE would typically be used to interface an external switch, which may be a room occupancy sensor, timer, on/off control from a BMS or any other suitably rated volt-free contacts.

Connections

The device is connected to the indoor unit via the CN06 socket on the indoor PCB and the indoor units supply terminals as illustrated.
 

Limitations

It is important to note that when an RBC-IT3-PE interface is used the standard 24hour timer functions within the Toshiba remote must not be selected to avoid conflict in switching commands.

The remote controller on/off button will be overridden whenever an interface is connected to socket CN06, regardless of whether the RBC-IT3PE is in use or not.

All other functions of the remote controller remain unaffected.

It is recommended that the power supply (230v.a.c.) be taken from the respective indoor unit, as indicated on the wiring diagram.

The field sourced time-switch may be located in any area. The a/c system will start when terminal 1 of the interface is energised and will override the remote controller on/off functions.

Due to the logic used, it is recommended that a minimum switching interval of 30 seconds be adopted. When first energised, it may be noticed that the indoor unit starts briefly and then stops, this is normal and does not indicate a fault with the system.


Downloads

 

 