TOSHIBA > TCC LINK CONTROLS > RBC-FDP2BMS-PE

 

 

 

 

RBC-FDP2BMS-PE
CONTROL INTERFACE
DI / SDI & VRF

RBC-FDP2BMS-PE

The FDP2- BMS is an interface that has the ability to accept inputs from an analogue BMS system. The inputs to the controller can be either voltage or resistance this can be configured on the FDP2-BMS. The device also has a relay output that closes in the event of a fault within the system.
 


Application

The FDP2-BMS has been designed to give a straightforward BMS solution it accepts voltage or restive inputs to set the following functions on the air conditioner.

Set point, Fan speed, Mode, Louver, On/Off and local remote Lock the inputs for these functions can be configured to be 0 to 10Volt or 0 to 10Kohms restive. A dipswitch SW1 selects the mode.

If the inputs go open circuit the FDP2-BMS assumes a default value for that input.  This is useful in the event of a failure in the BMS inputs to the device.

The FDP2-BMS can be customized to suit particular applications for a hotel or residential applicants where a specific control is required. An example is the set back requirements from a key card or a switch plate to match other electrical accessories in the room.

FDP2-BMS can be networked to give advanced functionality the FDP2-BMS can be used as a group controller to control large groups of multiples of eight indoor units. The controller can linked to other Realtime controls products to give standalone BMS applications for retail or residential applications. Further details of advanced control options are available on request.
 

Connections

The interface can be mounted within 500m of the indoor unit is contained in a metal housing it connects to the indoor unit via the AB network.
 

Limitations

The relay contacts are rated at 1A 24VAC or 1A30VDC.

Voltage inputs 0 to 10 V or Resistive inputs 0.4K Ohms to 10K Ohms.

 


Downloads



RBC-FDP2BMS-PE - Installation Manual

 