TOSHIBA > TCC LINK CONTROLS > RBC-CC163TLE2

 

 

- On/Off for 16 Units
- Enable/Disable All Function
- Connect DI via PCNT30TLE
 

RBC-CC163TLE2
ON/OFF CONTROLLER

RBC-CC163TLE2

The on/off controller is a product that is capable of operating 16 indoor units from a single location. The device consists of 16 individual on/off buttons, which allows any connected units to be enabled or disabled via a single button operation. It is also possible to enable or disable all of the connected units via single button operation.
 


Application

The device is ideally suited to locations where it may be necessary to remotely enable or disable indoor units. An example of this would be a hotel reception desk, where the receptionist may wish to enable a customer’s room air conditioning during the check-in process or disable it on the departure of a customer. Each of the on/off buttons has a label facility and again using the example of a hotel installation, the buttons could be labelled with a room number. For larger installations up to 4 controllers could be installed on one network, thus allowing 64 master indoor units to be controlled from one location.

The device also has the facility for interfacing time clock control, remote switching, remote run signal and remote fault indication from a set of auxiliary contacts.

 

Connections

The controller requires a 240 Volt single phase 3 Amp power supply, which connects directly to the mains input terminals on the rear of the device.

The two-core network cable should be screened and have a minimum cross-sectional area of 1.5mm for networks of up to 1000 meters. This should be increased to 2.5mm for networks of 1000 to 2000 meters total length. The network cable terminates at the U1/U3 and U2/U4 connections on the rear of the device.

Terminals A1, A2 and A3 are used to remotely operate all of the connected indoor units.

The indoor units can be enabled with a pulse voltage of 24 Volts applied for 0.5 seconds between terminals A1-A3 and disabled by applying the same voltage between terminals A2-A3.

Terminals B1, B2 and B3 provide dry contact outputs for connection to other systems. A relay contact will close between B3 and B1 indicating system operation and B3 and B2 indicating a fault on any connected units.

Terminal CN02 can be used to connect a 7day timer (RBC-EXW21E) or alternatively the RBC-SMTI interface lead can be connected and used as a means of remote switching.
 

Limitations

Individual control of 16 master indoor units, (7 slave units per master possible) All indoor units will be affected by any timer functions or remote operation signals.

Only on/off control is provided

 


Downloads


Wiring Diagram

 