TOSHIBA > TCC LINK CONTROLS > BACNET INTERFACE


 

- For BACnet over IP BMS
- 128 Indoors per server
- 8 Relay Interfaces per server
- Server requires 240V 3A supply
 

BACNET INTERFACE

BACNET INTERFACE

The BACnet solution allows the Toshiba indoor units to be connected to a BACnet over IP based BMS. The gateway uses all standard BACnet objects for the control and monitoring of each indoor unit.


 


Application

The BACnet solution is intended for use in systems where control of the air conditioning is being carried out by another system that is a part of the wider BMS for a large building. BACnet is a standard protocol adopted by many BMS companies as a standard network protocol they support.
 

Connections

The BACnet solution consists of several different components, which have been listed below. The maximum number of indoor units that may be controlled is 128 per Intelligent Server. Up to a maximum of eight Relay Interfaces can be connected per Intelligent Server.

Intelligent Server BMS-LSV4E

The intelligent server connects to the BACnet system by a network connection, usually to a local hub. The Relay Interfaces connect to the server by the RS485 network and up to eight Relay Interfaces may be connected, with a maximum of 128 indoor units. The Intelligent Server requires a 240V 3A mains supply.

BACnet Software BMS-STBN05E

The BACnet software is contained on a standard Compact Flash Card, which plugs directly into the Intelligent Server.

TCS Net Relay Interface BMS-IFLSV2E2

The Relay Interface connects to the Touch Screen Controller via the RS485 Network, (A & B connections). The air conditioner network connects to the U1 & U2 connections, with a maximum of 64 indoor units served. The Relay Interface requires a 240V 3 A mains supply.
 

Software

Site-specific software is written for the BACnet solution and then uploaded to the Intelligent Server. This gives site-specific names and locations, which are then presented to the BACnet network.
 

Limitations

The total length of the air conditioner U1/U2 network for each relay interface is as follows.

1.5mm2 Screened up to 1000m
2.5mm
2 Screened up to 2000m
The total length of the RS485 Network A/B
1.5mm
2 Screened up to 500m

The total length of the Ethernet cable from the Hub to the server should be a maximum of 100M

The IP Address range should not be used xx.xx.0.xx


Downloads


Wiring Diagram

 