TOSHIBA > BUSINESS RANGE > 600x600 FOUR-WAY CEILING CASSETTE

600x600 Four-way ceiling cassette


The classic choice

  • suited to installation in standard ceiling grid
  • easy access to control components via corner pockets, facilitating installation and height adjustment
  • high lift drain (850 mm)
  • high ceiling temperature control

Product Specification

Indoor Unit - MMU AP0071MH AP0091MH AP0121MH AP0151MH
Grille RBC-UM11PG(W)E RBC-UM11PG(W)E RBC-UM11PG(W)E RBC-UM11PG(W)E
Capacity Code 0.8 1.0 1.25 1.7
Cooling Capacity kW 2.2 2.8 3.6 4.5
Heating Capacity kW 2.5 3.2 4.0 5.0
Power Input kW 0.034 0.036 0.038 0.041
Air Flow (M/H/L) M3/h 552/462/378 570/468/378 594/504/402 660/552/468
Sound Pressure (H/M/L) dB(A) 36/32/28 37/33/28 37/33/29 40/35/30
Dimensions (HxWxD) mm 268x575x575 268x575x575 268x575x575 268x575x575
Grille Dimension (HWD) mm 27x700x700 27x700x700 27x700x700 27x700x700
Drain Diameter mm 25 25 25 25
Lift Pump Lift mm 850 850 850 850
Weight kg 17 17 17 17
Max. Operating Current A 0.28 0.30 0.31 0.34
Starting Current A 0.49 0.52 0.54 0.59
Suggested Fuse Size A 3 3 3 3
Power Supply V-ph-Hz 240-1-50 240-1-50 240-1-50 240-1-50
Indoor Unit - MMU AP0181MH
Grille RBC-UM11PG(W)E
Capacity Code 2.0
Cooling Capacity kW 5.6
Heating Capacity kW 6.3
Power Input kW 0.052
Air Flow (M/H/L) M3/h 762/642/522
Sound Pressure (H/M/L) dB(A) 44/39/34
Dimensions (HxWxD) mm 256 x 840 x 840
Grille Dimension (HWD) mm 35 x 950 x 950
Drain Diameter mm 25
Lift Pump Lift mm 850
Weight kg 17
Max. Operating Current A 0.42
Starting Current A 0.73
Suggested Fuse Size A 3
Power Supply V-ph-Hz 240-1-50

 

 


home - about us - toshiba - carrier - accessories - contact