TOSHIBA > FAQs > Digital Inverter Remote on/off & fault output
 

 

 

 

Question

How can we take a fault output and run signal from the system and control on/off remotely?

Solution

There are a number of ways to address this, please see options below

 

Digital Inverter - Remote on/off, fault & run outputs

Option 1 - Accessory CDL-BMS01

This lead plugs into CN61 of the indoor pcb.  Requires connection to other switching or display devices.

Wiring for CDL-BMS01 for Remote on/off
Wiring for CDL-BMS01 for Fault Output
Wiring for CDL-BMS01 for Run Signal
Wiring for CDL-BMS01 for Remote Locking



Option 2 - Accessory TCB-IFCB-4E

Remote location on/off control box wiring

This box is attached to the indoor board and can be used to remotely control (on/off only) and monitor alarm status for the attached indoor unit.  The accessory is connected to CN61 on the indoor PCB.
 

Note: Both these option give a stop fault.  If all faults are required then a FDP2 must be used.
 


 



 